problem
As an energy analyst, I need to know energy at point of interconnect, and that includes detailed transformer efficiency and losses, as well as ac collection losses and curtailment
solution
A transformer load / no-load model
alternatives
Roll your own, but then this risks everyone using slightly different, possibly flawed models, precisely one of the issues pvlib tries to solve
@kevinsa5 and @AdamRJensen brought this up during the PVPMC pvlib session. I'd like to take a stab at it if there are no objections. PlantPredict uses this very simple model from McCann, Lawrence , ABB Electrical Transmission and Distribution Reference, P.101.
I would also like to write a blog post that documents how to create a pull request for a pvlib upgrade using the transformer model as a real world example.
Reacted by Anton Driesse, Will Holmgren and Cliff Hansen
@kurt-rhee that would be great! FYI I skimmed around a bit in the reference but did not find the equation from the PlantPredict docs. For the pvlib function, we should cite a particular equation number or something to make it easier to find.
@kandersolar That is unfortunate, I looked through it as well and there is no mention of the equations that are in PlantPredict's documentation. I've also asked around internally and none of our EE's are familiar with the equation. Looking at the commit history, the function was last edited back in 2017 so whichever performance engineer wrote the spec for that code is likely long gone.
As for the path forward, I could upload the PlantPredict documentation to zenodo, or if that isn't sufficient for this type of work, I have reached out to First Solar to see if any of their engineers are familiar with the function.
I think it's possible to derive them based on definitions inspired by the load and no-load losses described in that ABB reference. It would still be nice to have a more explicit reference though. Here is the outline (note: all quantities in the following are normalized to the rated power of the transformer):
Assume load loss is proportional to the square of output power:
I think it would be best to reference an introductory electrical engineering text for the simplification of the losses as:
constant core losses, plus
quadratic winding losses
I've thrown out my textbooks decades ago, but I assume they still teach it so I hope some young engineer can suggest one.
The total loss is a vertically shifted parabola. Spec sheets give two points on that parabola, so you use these points to solve for the two coefficients of the parabola/transformer model, which we could call k_core and k_winding.
I think that all the calculations that go directly from specs to simulation needlessly and unfortunately obfuscate what is actually happening.
@adriesse An introductory electrical engineering text would be really nice I agree.
Would you be okay if I wrote a first version and created a PR with a reference to the worse text cited above along with Kevin's derivation just so that pvlib has some transformer model? My personal feeling is that a model with a not very good reference is better than no model at all, and we can always update the reference in the future.
It's my time to shine! I'll drop my two cents here: the only English book I see recommended in the subject I had regarding them, is Electric machinery fundamentals. Stephen J. Chapman.. Luckily it's easy to find freely on the Internet. Relevant section is 2.7, subsection "Transformer Efficiency", first equation is 2-65, p. 122 of the PDF, 102 of the textbook. Maybe it's a bit old, but I think it does the trick.
@echedey-ls & @kurt-rhee sorry I don’t understand the textbook reference. I can’t see how to manipulate it to the same form as @kandersolar derivation, Plant Predict, or SolarFarmer.
I see your point @mikofski . I understood from @adriesse comment were looking for a didactic reference, not an explicit reference with the same equations. Textually, the book states some losses are constant and other losses are quadratic with the current. The following changes explain @kandersolar first equation:
I think that all the calculations that go directly from specs to simulation needlessly and unfortunately obfuscate what is actually happening.
I do not see a way to simplify or meaningfully separate the math shown above. If the copper loss was defined to be proportional to $P_{in}^2$ then the equations would surely be much cleaner. But the only way to arrive at the SolarFarmer and PlantPredict model was to assume that the copper loss was instead proportional to $P_{out}^2$, requiring the nasty quadratic formula to solve for $P_{out}$.
If you have a cleaner way, I would be quite happy to see it!
@adriesse@kandersolar how about something like "abb_efficiency" so that it related to the reference? I don't think that PlantPredict or SolarFarmer should get credit for the model since neither of us came up with it. I'm sure @mikofski would agree.
Thank you so much @kurt-rhee , @echedey-ls , @kandersolar , @adriesse , & everyone who helped on this. It feels so gods to see this issue/feature-request closed after 3 years! Amazing!
Activity
adriesse commentedon Aug 27, 2021
I think this would be a nice addition. The modelling is relatively easy and spec sheets often have the needed info.
kurt-rhee commentedon May 10, 2024
Hey @mikofski,
@kevinsa5 and @AdamRJensen brought this up during the PVPMC pvlib session. I'd like to take a stab at it if there are no objections. PlantPredict uses this very simple model from McCann, Lawrence , ABB Electrical Transmission and Distribution Reference, P.101.
https://terabase.atlassian.net/servicedesk/customer/portal/3/article/1292304413
kurt-rhee commentedon May 10, 2024
I would also like to write a blog post that documents how to create a pull request for a pvlib upgrade using the transformer model as a real world example.
mikofski commentedon May 10, 2024
If it helps I did some nuts & bolts talks at UC BIDS a few years back:
kurt-rhee commentedon May 11, 2024
Mark those are awesome references, I will definitely riff off of them.
kandersolar commentedon May 13, 2024
@kurt-rhee that would be great! FYI I skimmed around a bit in the reference but did not find the equation from the PlantPredict docs. For the pvlib function, we should cite a particular equation number or something to make it easier to find.
mikofski commentedon May 14, 2024
here is the SolarFarmer equation. I don’t know the reference. Is it similar to Plant Predict?
kurt-rhee commentedon May 14, 2024
@kandersolar That is unfortunate, I looked through it as well and there is no mention of the equations that are in PlantPredict's documentation. I've also asked around internally and none of our EE's are familiar with the equation. Looking at the commit history, the function was last edited back in 2017 so whichever performance engineer wrote the spec for that code is likely long gone.
As for the path forward, I could upload the PlantPredict documentation to zenodo, or if that isn't sufficient for this type of work, I have reached out to First Solar to see if any of their engineers are familiar with the function.
kurt-rhee commentedon May 14, 2024
@mikofski Looks like SolarFarmer and PlantPredict have different models for transformer losses.
mikofski commentedon May 15, 2024
@kurt-rhee I did a test and actually they’re identical!
Transformers.xlsx
They’re just algebraic manipulations of each other. Now who knows the reference? Is this just common power electronics? Maybe any textbook?
kandersolar commentedon May 15, 2024
I think it's possible to derive them based on definitions inspired by the load and no-load losses described in that ABB reference. It would still be nice to have a more explicit reference though. Here is the outline (note: all quantities in the following are normalized to the rated power of the transformer):
Assume load loss is proportional to the square of output power:
Total loss is the variable load loss, plus a constant no-load loss:
Conservation of energy:
Now use quadratic formula to solve for$P_{\mathrm{out}}$ as a function of $P_{\mathrm{in}}$ :
where
So:
(the positive root must be the correct one, if$P_{\mathrm{out}}$ is to be positive)
2 remaining items
adriesse commentedon May 16, 2024
I think it would be best to reference an introductory electrical engineering text for the simplification of the losses as:
I've thrown out my textbooks decades ago, but I assume they still teach it so I hope some young engineer can suggest one.
The total loss is a vertically shifted parabola. Spec sheets give two points on that parabola, so you use these points to solve for the two coefficients of the parabola/transformer model, which we could call
k_coreandk_winding.I think that all the calculations that go directly from specs to simulation needlessly and unfortunately obfuscate what is actually happening.
kurt-rhee commentedon May 16, 2024
@adriesse An introductory electrical engineering text would be really nice I agree.
Would you be okay if I wrote a first version and created a PR with a reference to the worse text cited above along with Kevin's derivation just so that pvlib has some transformer model? My personal feeling is that a model with a not very good reference is better than no model at all, and we can always update the reference in the future.
kurt-rhee commentedon May 16, 2024
@mikofski and @kandersolar
Seriously bravo thank you for all of the work you guys did.
echedey-ls commentedon May 16, 2024
It's my time to shine! I'll drop my two cents here: the only English book I see recommended in the subject I had regarding them, is
Electric machinery fundamentals. Stephen J. Chapman.. Luckily it's easy to find freely on the Internet. Relevant section is 2.7, subsection "Transformer Efficiency", first equation is 2-65, p. 122 of the PDF, 102 of the textbook. Maybe it's a bit old, but I think it does the trick.kurt-rhee commentedon May 17, 2024
@echedey-ls Awesome!
http://powerunit-ju.com/wp-content/uploads/2016/11/Book-Fundamentals-of-Electric-Machinery-by-Chapman-4ed.pdf
Here is a link to the textbook I found online.
mikofski commentedon May 17, 2024
@echedey-ls & @kurt-rhee sorry I don’t understand the textbook reference. I can’t see how to manipulate it to the same form as @kandersolar derivation, Plant Predict, or SolarFarmer.
echedey-ls commentedon May 17, 2024
I see your point @mikofski . I understood from @adriesse comment were looking for a didactic reference, not an explicit reference with the same equations. Textually, the book states some losses are constant and other losses are quadratic with the current. The following changes explain @kandersolar first equation:
Notation is different; how to determine$L_{full,load} \enspace\text{or}\enspace k_{Cu}$ is a matter of solving for it in the first equation.
Thanks for putting the image @kurt-rhee , sometimes I forget the most obvious features of github 💀
kandersolar commentedon May 22, 2024
I do not see a way to simplify or meaningfully separate the math shown above. If the copper loss was defined to be proportional to$P_{in}^2$ then the equations would surely be much cleaner. But the only way to arrive at the SolarFarmer and PlantPredict model was to assume that the copper loss was instead proportional to $P_{out}^2$ , requiring the nasty quadratic formula to solve for $P_{out}$ .
If you have a cleaner way, I would be quite happy to see it!
adriesse commentedon May 23, 2024
I'm afraid I've reached my pro bono limit on this one. Perhaps just give it another name like "plantpredict_solarfarmer" rather than "simple"! :)
kurt-rhee commentedon May 23, 2024
@adriesse @kandersolar how about something like "abb_efficiency" so that it related to the reference? I don't think that PlantPredict or SolarFarmer should get credit for the model since neither of us came up with it. I'm sure @mikofski would agree.
cwhanse commentedon May 23, 2024
+1 for
abb_efficiencyif we change the reference to ABB's 1997 publication, which is a derivative work of the 1950s Westinghouse book.mikofski commentedon May 24, 2024
Works for me
mikofski commentedon Jun 19, 2024
Thank you so much @kurt-rhee , @echedey-ls , @kandersolar , @adriesse , & everyone who helped on this. It feels so gods to see this issue/feature-request closed after 3 years! Amazing!